Specifications
Type
Paramete
Type
Paramete
Type
Temperature Controller (RTD, Type J, K, L, N, R, S)
Voltage - Supply
24VAC/DC
Number of Characters Per Row
4, 4
Control Method
On/Off, Proportional (PID)
Display Characters - Height
0.394" (10.00mm), 0.295" (7.50mm)
Input Range
-200°C ~ 1760°C
Mounting Type
Panel Mount
Features
Heater Fault Detection
Output Type
Relay (3)
Termination Style
Screw Terminal
Communications
RS-485
Display Type
LED - Dual Color Characters
Ingress Protection
IP54 - Dust Protected, Water Resistant
Panel Cutout Dimensions
Square - 45.00mm x 45.00mm
Overview

DESCRIPTION

· MIC48 with RS 485 link, part number 89422402, is a versatile controller designed for heating and/or cooling functions.



FEATURES

· 2 independent alarms for enhanced safety and monitoring.

· Load break detection to ensure continuous operation.

· 2 remotely selectable setpoints for flexible control.

· Manual/automatic power adjustment for user convenience.

· RS 485/MODBUS-JBUS serial communication option for integration.

· Relay output with 24 V AC/DC supply voltage.

· Supply range of 100 to 240 VAC, 24 VAC/DC with 50/60 Hz frequency.

· Power consumption up to 8 VA.

· 4-digit, 7-segment red LED display for measurements.

· 4-digit, 7-segment green LED display for setpoints.

· PID control algorithm with auto-tune and adaptive tune (SMART).

· Sampling times of 250 ms for linear input and 500 ms for TC and RTD inputs.

· Proportional band settings from 1.0% to 100% for heating or cooling.

· Integral time from 20 s to 20 min; derivative time from 1 s to 10 min.

· Cycle times from 1 s to 200 s for both heating and cooling.

· Supports thermocouples J, K, R, S, N, L, and RTD Pt100.

· Automatic cold junction compensation for thermocouples.

· Input impedance greater than 1 MΩ.

· Current transformer input for load break monitoring.



APPLICATIONS

· Ideal for systems requiring precise temperature control with heating and/or cooling functions.

· Suitable for environments needing remote setpoint selection and power adjustment.

· Effective in applications where load break detection and independent alarms are critical.

· Compatible with systems utilizing RS 485/MODBUS-JBUS communication protocols.

Shopping Guide
Purchase

No need to register to order from JMBom Electronics, but signing in lets you track your order like a pro. Give it a try for a smoother shopping ride.

Means

Easy peasy! Pay your way with PayPal, Credit Card, or wire transfer in USD. We've got you covered.

RFQ(Request for Quotations)

Get the freshest prices and stock updates by asking for a quote! Our sales team will shoot you an email within a day. It's that simple.

IMPORTANT NOTICE

1. Look out for your order details in your inbox! (If it's missing, check the spam folder just in case.)

2. Our sales manager will double-check the order and keep you posted on any price or stock changes. No worries, we've got you covered. 

picture_01

Shipping Rate

We ship orders once a day around 5 p.m., except Sunday. Once shipped, the estimated delivery time depends on the courier company you choose, usually 5-7 working days.

picture_02

Shipping Methods

We provide DHL, FedEx, UPS, EMS, SF Express, and Registered Air Mail international shipping.

picture_11
picture_03

Payment

You can pay the orders on the website directly or pay by wire transfer offline. We support: Paypal、VISA、Credit Card.

pay-img-1pay-img-2pay-img-3pay-img-4